HCM(WXM)
RXM2LB2P7
Delivery time:in stock
Range of product
Harmony Electromechanical Relays
Series name
Miniature
Product or component type
Plug-in relay
Device short name
RXM
Coil interference suppression
Without
utilisation coefficient
20 %
Sale per indivisible quantity
10
Contacts type and composition
2 C/O
Contact operation
Standard
[Uc] control circuit voltage
230 V AC 50/60 Hz
[Ithe] conventional enclosed thermal current
5 A at -40…55 °C
Status LED
With
Control type
Without push-button
[Ui] rated insulation voltage
250 V conforming to IEC
[Uimp] rated impulse withstand voltage
4 kV during 1.2/50 µs conforming to IEC 61810-7
Contacts material
Silver alloy (Ag/Ni)
[Ie] rated operational current
5 A (AC-1/DC-1) NO conforming to IEC
2.5 A (AC-1/DC-1) NC conforming to IEC
1 A at 28 V (DC-13) NO
Minimum switching current
10 mA
Maximum switching voltage
250 V AC
28 V DC
Minimum switching voltage
17 V
Load current
5 A at 250 V AC
5 A at 28 V DC
Maximum switching capacity
1250 VA AC
140 W DC
Minimum switching capacity
170 mW
Operating rate
<= 1200 cycles/hour under load
<= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles for resistive load
50000 cycles, 1 A at 28 V, DC-13 NO
Average coil consumption in VA
1.2 AC
Drop-out voltage threshold
>= 0.15 Uc AC
Operating time
20 ms between coil de-energisation and making of the Off-delay contact
20 ms between coil energisation and making of the On-delay contact
Average resistance
16500 Ohm at 23 °C +/- 15 %
Rated operational voltage limits
184...253 V AC
Protection category
RT I
Test levels
Level A group mounting
Operating position
Any position
CAD overall width
21 mm
CAD overall height
27 mm
CAD overall depth
46 mm
Net weight
0.031 kg
Dielectric strength
2000 V AC between coil and contact with basic insulation
2000 V AC between poles with basic insulation
1000 V AC between contacts with micro disconnection
Safety reliability data
B10d = 100000
Standards
CE
EN/IEC 61810-1 (iss. 2)
Ambient air temperature for storage
-40…85 °C
Ambient air temperature for operation
-40…55 °C
Vibration resistance
3 gn, amplitude = +/- 1 mm (f = 10…50 Hz)operating conforming to EN/IEC 60068-2-6
6 gn, amplitude = +/- 1 mm (f = 10…50 Hz)not operating conforming to EN/IEC 60068-2-6
IP degree of protection
IP40 conforming to EN/IEC 60529
Pollution degree
3
Shock resistance
30 gn for not operating conforming to EN/IEC 60068-2-27
10 gn for in operation conforming to EN/IEC 60068-2-27