HCM
LUCA1XBL
Delivery time:in stock
Range
TeSys
Range of Product
TeSys Ultra
Product name
TeSys Ultra
Device short name
LUCA
Product or Component Type
Standard control unit
Device Application
Motor control
Motor protection
Product Specific Application
Basic protection requirements for motor starters: overload and short-circuit
main function available
Protection against overload and short-circuit
Protection against phase failure and phase imbalance
Manual reset
Earth fault protection
Product compatibility
Power base LUB12
Power base LUB32
Power base LUB38
Power base LUB120
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B12BL
Reversing contactor breaker LU2B32BL
Reversing contactor breaker LU2B38BL
[Ue] rated operational voltage
690 V AC
Network frequency
40...60 Hz
Load type
3-phase motor self-cooled
Utilisation category
AC-44
AC-43
AC-41
Motor power kW
0.25 kW 400...440 V AC 50/60 Hz
rated motor current adjustment range
0.35…1.4 A
Thermal overload class
Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2
Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508
Tripping threshold
14.2 x Ir +/- 20 %
Phase failure sensitivity
Yes
[Uc] control circuit voltage
24 V DC
Control circuit voltage limits
20...27 V DC 24 V in operation
14.5 V DC 24 V drop-out
Typical current consumption
130 mA 24 V DC I maximum while closing with LUB12
220 mA 24 V DC I maximum while closing with LUB32
220 mA 24 V DC I maximum while closing with LUB38
60 mA 24 V DC I rms sealed with LUB12
80 mA 24 V DC I rms sealed with LUB32
80 mA 24 V DC I rms sealed with LUB38
Heat dissipation
2 W control circuit with LUB12
3 W control circuit with LUB32
3 W control circuit with LUB38
Operating time
35 ms opening with LUB12 control circuit
35 ms opening with LUB32 control circuit
35 ms opening with LUB38 control circuit
70 ms closing with LUB12 control circuit
70 ms closing with LUB32 control circuit
70 ms closing with LUB38 control circuit
Standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
Product Certifications
CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
[Ui] rated insulation voltage
690 V IEC 60947-6-2
600 V UL 60947-4-1
600 V CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-6-2
Safe separation of circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Fixing mode
Plug-in front face)
Width
1.77 in (45 mm)
Height
2.60 in (66 mm)
Depth
2.36 in (60 mm)
Net Weight
0.30 lb(US) (0.135 kg)
Compatibility code
LUCA
IP degree of protection
IP20 front panel and wired terminals IEC 60947-1
IP20 other faces IEC 60947-1
IP40 front panel outside connection zone IEC 60947-1
Protective treatment
TH IEC 60068
Ambient air temperature for operation
-13…158 °F (-25…70 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Operating altitude
6561.68 ft (2000 m)
Fire resistance
1760 °F (960 °C) parts supporting live components IEC 60695-2-12
1202 °F (650 °C) IEC 60695-2-12
Shock resistance
10 gn power poles open IEC 60068-2-27
15 gn power poles closed IEC 60068-2-27
Vibration resistance
2 gn 5…300 Hz power poles open IEC 60068-2-6
4 gn 5…300 Hz power poles closed IEC 60068-2-6
Resistance to electrostatic discharge
8 kV 3 in open air IEC 61000-4-2
8 kV 4 on contact IEC 61000-4-2
Resistance to radiated fields
9.14 V/m (10 V/m) 3 IEC 61000-4-3
Resistance to fast transients
2 kV 3 serial link IEC 61000-4-4
4 kV 4 all circuits except for serial link IEC 61000-4-4
Immunity to radioelectric fields
10 V IEC 61000-4-6
Immunity to microbreaks
3 ms
Immunity to voltage dips
70 % / 500 ms IEC 61000-4-11