Auxiliary Circuit 690 V AC
Auxiliary Circuit 250 V DC
Main Circuit 690 V AC
Main Circuit 220 V DC
Rated Frequency (f):
Control Circuit DC
Main Circuit 60 Hz
Main Circuit 50 Hz
Main Circuit DC
Rated Impulse Withstand Voltage (Uimp):
Auxiliary Circuit 6 kV
Main Circuit 6 kV
Rated Insulation Voltage (Ui):
690 V
acc. to UL/CSA 600 V
Number of Main Contacts NC:
0
Number of Main Contacts NO:
3
Rated Operational Current AC-1 (Ie):
(220 / 240 V) 40 °C 12 A
(220 / 240 V) 55 °C 12 A
(380 / 440 V) 40 °C 12 A
(380 / 440 V) 55 °C 12 A
(690 V) 40 °C 6 A
(690 V) 55 °C 6 A
Rated Operational Power AC-3 (Pe):
(230 V) Three Phase 2.2 kW
(400 V) Three Phase 4 kW
(500 V) Three Phase 4 kW
(690 V) Three Phase, NO 3 kW
Rated Short-time Withstand Current Low Voltage (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 64 A
Number of Auxiliary Contacts NC:
1
Number of Auxiliary Contacts NO:
0
Rated Operational Current AC-15 (Ie):
(24 V) 4 A
(120 V) 4 A
(500 V) 2 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie):
(24 V) 2.5 A
(110 V) 0.7 A
(220 / 240 V) 0.4 A
Conventional Free-air Thermal Current (Ith):
Main Circuit 12 A
Rated Control Circuit Voltage (Uc):
24 V DC
Coil Operating Limits:
(acc. to IEC 60947-4-1) for DC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C)
Degree of Protection:
Auxiliary Circuit Terminals IP20
Control Circuit Terminals IP20
Main Circuit Terminals IP20
Mechanical Durability:
10000000 cycle
Minimum Switching Capacity:
Auxiliary Circuit 17 V
Auxiliary Circuit 5 mA
Maximum Electrical Switching Frequency:
(AC-1) 300 cycles per hour
(AC-15) 600 cycles per hour
(AC-3) 600 cycles per hour
(DC-1) 600 cycles per hour
(DC-13) 600 cycles per hour
(DC-3) 600 cycles per hour
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Power Loss:
at Rated Operating Conditions per Pole 2 W
at Rated Operating Conditions AC-1 per Pole 1 W
Standards:
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1
UL 60947-4-1
Remarks:
No CA6 or CAF6 mountable
Technical UL/CSA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Full Load Amps Motor Use:
(115 V AC) Single Phase 5.8 A
(200 V AC) Three Phase 4.8 A
(220 ... 240 V AC) Three Phase 6.8 A
(230 V AC) Single Phase 4.9 A
(440 ... 480 V AC) Three Phase 4.8 A
(550 ... 600 V AC) Three Phase 1.7 A
Horsepower Rating UL/CSA:
(115 V AC) Single Phase 0.25 Hp
(200 V AC) Three Phase 1 Hp
(220 ... 240 V AC) Three Phase 2 Hp
(230 V AC) Single Phase 0.5 Hp
(440 ... 480 V AC) Three Phase 3 Hp
(550 ... 600 V AC) Three Phase 1 Hp