HCM
QUINT-UPS/ 24DC/ 24DC/40
Delivery time:in stock
| DC operation | |
| Input voltage | 24 V DC |
| Nominal input voltage range | 24 V DC |
| Input voltage range | 18 V DC ... 30 V DC |
| Input voltage range DC | 18 V DC ... 30 V DC |
| Voltage type of supply voltage | DC |
| Buffer period | 0.5 h (With battery module 38 AH) |
| Current consumption | 51.9 A (maximum, mains operation) |
| 10.6 mA (No load, mains operation) | |
| 6.9 A (Charging, mains operation) | |
| Fixed backup threshold | ≤ 22 V DC |
| Variable connect threshold | 1 V/0.1 s |
| Efficiency | > 99 % (Mains operation, with charged energy storage) |
| 98 % (Battery operation) | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 18 V DC ... 30 V DC |
| Nominal output current (IN) | 40 A (-25 °C ... 50 °C) |
| Output current limit | In mains mode according to connected upstream current limiting device |
| > 45 A (Battery operation) | |
| Bridging time | 3600 s |
| Derating | 60 °C ... 70 °C (2.5%/K) |
| 60 °C ... 70 °C (2.5%/K) | |
| Output power | 960 W |
| Power dissipation | 2.8 W (Mains operation) |
| 13 W (Mains operation) | |
| 3.51 W (Battery operation) | |
| 16.4 W (Battery operation) | |
| Connection in parallel | yes, up to 2 modules with redundancy module |
| 2 (Devices) | |
| Connection in series | No |
| no | |
| Mains operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 18 V DC ... 30 V DC |
| Nominal output current (IN) | 40 A (-25 °C ... 50 °C) |
| POWER BOOST (IBoost) | 45 A (-25°C ... 40°C) |
| Selective Fuse Breaking (ISFB) | 215 A (-25 °C ... 60 °C) |
| Duration | 12 ms (SFB technology) |
| Battery operation | |
| Nominal output voltage | 24 V DC |
| Output voltage range | 19.2 V DC ... 27.6 V DC (UOUT = UBAT - 0,5 V DC) |
| Nominal output current (IN) | 40 A (-25 °C ... 60 °C) |
| POWER BOOST (IBoost) | 45 A (-25°C ... 40°C) |
| Selective Fuse Breaking (ISFB) | 215 A (-25 °C ... 60 °C) |
| Duration | 15 ms (SFB technology) |
| Signal: Alarm | |
| Output description | Relay (floating) |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Continuous load current | ≤ 100 mA |
| Signal: Battery charge | |
| Output description | Relay (floating) |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Output voltage | 24 V |
| Continuous load current | ≤ 100 mA |
| Signal: Battery mode | |
| Output description | Relay (floating) |
| Maximum switching voltage | ≤ 30 V AC/DC |
| Output voltage | 24 V |
| Continuous load current | ≤ 100 mA |
| Nominal voltage UN | 24 V DC |
| End-of-charge voltage | 24 V DC ... 29 V DC (temperature compensated) |
| Charging current | 0.2 A ... 5 A |
| Nominal capacity range | 7 Ah ... 200 Ah |
| Battery presence check/time interval | 1 min. |
| Battery presence check (cyclic) | 60 s |
| IQ technology | Yes |
| Temperature compensation | 42 mV/K (preset) |
| Temperature compensation (preset) | 42 mV/K |
| Network management | Yes |
| Input | |
| Connection method | Screw connection |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 8 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
| Output | |
| Connection method | Screw connection |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 16 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 16 mm² |
| Conductor cross section AWG min. | 8 |
| Conductor cross section AWG max. | 6 |
| Stripping length | 10 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.2 Nm |
| Tightening torque max | 1.5 Nm |
| Signal | |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 4 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Screw thread | M4 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
| Interface | IFS (Interface system data port) |
| Types of signaling | LED |
| Relay contact | |
| Interface/software | |
| Signal output | |
| Signalization designation | Power In OK |
| Status display | LED |
| Note on status display | Static to |
| Static to | |
| Signal output: Switching output | |
| Signalization designation | Alarm |
| Status display | LED |
| Note on status display | Static to |
| Color | red |
| Note on status display | Static to |
| Signal output: Switching output | |
| Signalization designation | Battery charge |
| Status display | LED bar graph |
| Note on status display | dynamic |
| Color | green/red |
| Note on status display | dynamic |
| Signal output: Switching output | |
| Signalization designation | Battery mode |
| Status display | LED |
| Note on status display | Static to |
| Color | yellow |
| Note on status display | Static to |
| Insulation voltage input/output | 500 V DC |
| Insulation voltage input, output / housing | 750 V DC |
| Product type | Uninterruptible power supply |
| IQ technology | Yes |
| MTBF (IEC 61709, SN 29500) | > 500000 h (40 °C) |
| Insulation characteristics | |
| Protection class | III |
| Life expectancy (electrolytic capacitors) | |
| Time | 147792 h |
| Width | 47 mm |
| Height | 130 mm |
| Depth | 125 mm |
| Installation dimensions | |
| Installation distance right/left | 5 mm / 5 mm |
| Installation distance top/bottom | 50 mm / 50 mm |
| Alternative assembly | |
| Width | 123 mm |
| Height | 130 mm |
| Depth | 51 mm |
| Mounting type | DIN rail mounting |
| Assembly instructions | alignable: horizontal 5 mm, vertical 50 mm |
| Mounting position | horizontal DIN rail NS 35, EN 60715 |
| Color | aluminium |
| Housing material | Metal |
| Type of housing | Aluminum (AlMg3) |
| Hood version | Galvanized sheet steel, free from chrome (VI) |
| Housing material | Steel sheet, zinc-plated |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -25 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Climatic class | 3K3 (in acc. with EN 60721) |
| Max. permissible relative humidity (operation) | ≤ 95 % (25 °C, non-condensing) |
| Shock | 18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
| Vibration (operation) | < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
| 15 Hz ... 150 Hz, 2.3g tv = 90 min. | |