Number of inputs and outputs | Number of analog outputs: 1 |
---|---|
Measuring range [°C] | -50...200 |
Process connection | threaded connection G 1/2 sealing cone |
Installation length EL [mm] | 50 |
Measuring element | 1 x Pt 1000; (to DIN EN 60751, class A) |
---|---|
Media | liquids and gases |
Pressure rating [bar] | 160 |
Vacuum resistance [mbar] | -1000 |
MAWP (for applications according to CRN) [bar] | 160 |
Operating voltage [V] | 18...32 DC; (cULus - Class 2 source required) |
---|---|
Current consumption [mA] | < 50 |
Protection class | III |
Reverse polarity protection | yes |
Power-on delay time [s] | 2 |
Number of inputs and outputs | Number of analog outputs: 1 |
---|
Total number of outputs | 1 |
---|---|
Output signal | analog signal; IO-Link; (configurable) |
Number of analog outputs | 1 |
Analog current output [mA] | 4...20 |
Max. load [Ω] | 250; ((18...19 V); 19...32 V: 300 Ω) |
Short-circuit protection | yes |
Overload protection | yes |
Measuring range [°C] | -50...200 |
---|---|
Factory setting | 0...100 °C |
Resolution of analog output [K] | 0.04 |
---|
Precision analog output [K] | ± 0,3 + (± 0,1 % MS) |
---|---|
Temperature coefficient [% of the span / 10 K] | 0,1; (In case of deviation from the reference condition 25 ± 5 °C) |
Dynamic response T05 / T09 [s] | < 0,5 / < 2 |
---|
Communication interface | IO-Link |
---|---|
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
Ambient temperature [°C] | -25...80 | |||
---|---|---|---|---|
Note on ambient temperature |
|
|||
Storage temperature [°C] | -40...100 | |||
Protection | IP 67; IP 68; IP 69K |
EMC |
|
||||
---|---|---|---|---|---|
Shock resistance |
|
||||
Vibration resistance |
|
||||
MTTF [years] | 334 | ||||
Note on approval |
|
||||
UL approval |
|
Weight [g] | 182 |
---|---|
Dimensions [mm] | Ø 18.7 |
Material | stainless steel (1.4404 / 316L); PEI; FKM |
Materials (wetted parts) | stainless steel (1.4404 / 316L) electropolished |
Tightening torque [Nm] | 30...50 |
Process connection | threaded connection G 1/2 sealing cone |
Surface characteristics Ra/Rz of the wetted parts | Ra: < 0.8 |
Probe diameter [mm] | 6 |
Installation length EL [mm] | 50 |