H3DS-ML
1
  • H3DS-ML
2
views: 504

H3DS-ML

Rate:
0.0000/5

( 0 reviews )

Item NO.: V028312 MOQ: 0
Weight:    0.3kgs
Package Size:  
 Price:
$50.00
 Qty:
      $50.00
 Shipping:   Calculate Shipping Cost

ZZ

H3DS-ML

delivery time:in stock



24 to 230 VAC 50/60 Hz, 24 to 48 VDC, Input Voltage input, Output Time-limit: SPDT, ON delay/Flicker OFF start/Flicker ON start/Signal ON/OFF delay/Signal OFF delay/Interval/One shot output, Time range: 0.1 to 1.2 s (7 range), Terminal blocks

Rated power supply voltage 24 to 230 VAC 50/60 Hz
24 to 48 VDC Ripple 20% max.
Input signals Start
Input method Voltage input
Control output (Type) Time-limit: SPDT
Connecting method Terminal blocks
Rated power supply voltage 24 to 230 VAC 50/60 Hz
24 to 48 VDC Ripple 20% max.
Allowable voltage variable range 85% to 110% of rated voltage
Input signals Start
Input method Voltage input
Voltage input High level: 20.4 to 253 VAC/20.4 to 52.8 VDC
Low level: 0 to 2.4 VAC/VDC
Power consumption 32 VA max. (at 230 VAC)
3.0 W max. (at 230 VAC)/0.7 W max. (at 24 VDC)/1.4 W max. (at 48 VDC)
Reset voltage 2.4 VDC/VAC max.
Number of time ranges 7
Operation mode ON delay, Flicker OFF start, Flicker ON start, Signal ON/OFF delay, Signal OFF delay, Interval, One shot output
Control output (Type) Time-limit: SPDT
Control output (Contact output) Resistive load: 5 A at 250 VAC (cosφ=1)/5 A at 30 VDC/0.5 A max. at 125 VDC
Inductive load: 1 A at 250 VAC (cosφ=0.3)
Minimum applicable load: 10 mA at 5 VDC (failure level: P Reference value)
Ambient temperature range Operating: -10 to 55 ℃ (with no icing)
Storage: -25 to 65 ℃ (with no icing)
Ambient humidity range Operating: 35 to 85%
Accuracy of operating time ±1% FS max. (±1% ±10 ms in a range of 1.2 s)
Setting error ±10% FS ±0.05 s max.
Influence of voltage ±0.7% FS max. (±0.7% ±10 ms in a range of 1.2 s)
Influence of temperature ±5% FS max. (±5% ±10 ms in a range of 1.2 s)
Insulation resistance 100 MΩ min. (at 500 VDC)
Dielectric strength Between current carrying metal parts and non-current carrying metal parts: 2,000 VAC 50/60 Hz 1 min
Between control output terminals and operating circuit: 2,000 VAC 50/60 Hz 1 min
Between non-continuous contacts: 1,000 VAC 50/60 Hz 1 min
Impulse withstand voltage Between power terminals: 5 kV
Between current carrying terminals and exposed non-current carrying metal parts: 5 kV
Noise immunity ±1.5 kV square-wave noise by noise simulator (pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Mulfunction: 4 kV, Destruction: 8 kV
Vibration resistance Destruction: 10 to 55 Hz, 0.75 mm single amplitude each in 3 directions for 2 h
Malfunction: 10 to 55 Hz, 0.5 mm single amplitude each in 3 directions for 10 min
Shock resistance Destruction: 1,000 m/s2, 3 times each in 6 directions
Malfunction: 100 m/s2, 3 times each in 6 directions
Life expectancy (relay output) Electrical: 100,000 operations min. (5 A at 250 VAC, resistive load at 360 operations/h)
Mechanical: 10 million operations min. (under no load at 1,800 operations/h)
Degree of protection IP30 (Terminal Block: IP20)
Connecting method Terminal blocks
Weight Approx. 100 g

 