ZLL(YL)
LC1D098M7
delivery time:in stock
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
AC-3
AC-3e
AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 250 V DC
[Ie] rated operational current
20 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
[Uc] control circuit voltage
220 V AC 50/60 Hz
Compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Contact compatibility
M6
Protective cover
With
[Ith] conventional free air thermal current
20 A 140 °F (60 °C) power circuit
10 A 140 °F (60 °C) signalling circuit
Irms rated making capacity
250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
Rated breaking capacity
250 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current
105 A 104 °F (40 °C) - 10 s power circuit
210 A 104 °F (40 °C) - 1 s power circuit
30 A 104 °F (40 °C) - 10 min power circuit
61 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating
10 A gG signalling circuit IEC 60947-5-1
25 A gG <= 690 V type 1 power circuit
20 A gG <= 690 V type 2 power circuit
Average impedance
2.5 mOhm - Ith 25 A 50 Hz power circuit
Power dissipation per pole
1.56 W AC-1
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15 Mcycles
Electrical durability
0.3 Mcycles 20 A AC-1 <= 690 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…140 °F (-40…60 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
Inrush power in VA
70 VA 60 Hz 0.75 68 °F (20 °C))
70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-in power consumption in VA
7.5 VA 60 Hz 0.3 68 °F (20 °C))
7 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation
2…3 W 50/60 Hz
Operating time
12...22 ms closing
4...19 ms opening
Maximum operating rate
3600 cyc/h 140 °F (60 °C)