MODEL | BATF-32S1 | BATF-10S1 | BATF-49S1 | BATF-65S1 | BATF-80S1 | BATF-98S1 | BATF-114S1 | BATF-130S1 | BATF-145S1 | BATF-160S1 | BATF-179S1 | BATF-196S1 | |||
machine group special nature |
Refrigerating capacity | Kw | 32.6 | 40 | 48.8 | 65.2 | 78.9 | 97.8 | 114 | 130.4 | 145.2 | 159.2 | 179.2 | 195.6 | |
Air volume | m3/h | 6000 | 7000 | 8000 | 11000 | 14000 | 16000 | 18500 | 21000 | 24000 | 27000 | 29500 | 32000 | ||
Off balance pressure | Pa | 200 | 220 | 250 | 300 | 340 | 390 | 410 | 430 | 465 | 500 | 536 | 568 | ||
Control temperature | °C | 15~27 | |||||||||||||
Noise | dB(A) | ≦60 | ≦65 | ≦70 | ≦70 | ≦75 | ≦75 | ≦78 | ≦78 | ≦78 | ≦80 | ≦80 | ≦80 | ||
Power | 3ph~50HZ~380V | ||||||||||||||
Unit power | KW | 9.7 | 10.5 | 13 | 19 | 23.1 | 28 | 31 | 33.9 | 40 | 46.2 | 50.6 | 55 | ||
Pressure shrink machine |
Number x power | Kw | 1x7.5 | 1x8.8 | 2X5.5 | 2X7.5 | 2x8.8 | 2X11.0 | 11.0+14.7 | 2x14.7 | 14.7+18.4 | 2X18.4 | 11+2X14.7 | 3X14.7 | |
system cold system Unification |
cold Coagulation implement |
type | Shell and tube type | ||||||||||||
Water quantity | m3/h | 8 | 10 | 12 | 16 | 20 | 24 | 28 | 32 | 36 | 40 | 44 | 48 | ||
Takeover specification | inch | 3/2 | 3/2 | 3/2 | 2 | 2 | 5/2 | 5/2 | 5/2 | 3 | 3 | 3 | 3 | ||
Working substance | R22 | ||||||||||||||
Throttling mode | Expansion valve | ||||||||||||||
Refrigerant charge | Kg | 6 | 7 | 2X55 | 2X6 | 2X7 | 2X7.5 | 7.5+9.5 | 2X9.5 | 9.5+10.5 | 2X10.5 | 7.5+2X9.5 | 3X9.5 | ||
through wind system Unification |
Fan motor power | Kw | 2.2 | 2.2 | 3 | 4 | 5.5 | 5.5 | 7.5 | 11 | 11 | 11 | 11 | 11 | |
Filter screen |
Nylon net |