1756-A5XT АB module
delivery time:4 weeks
Technical Data
1756 ControlLogix Chassis Specifications
Catalog Numbers 1756-A4/B, 1756-A4K/B, 1756-A4/C, 1756-A4K/C, 1756-A7/B, 1756-A7K/B, 1756-A7/C, 1756-A7K/C,
1756-A10/B, 1756-A10K/B, 1756-A10/C, 1756-A10K/C, 1756-A13/B, 1756-A13K/B, 1756-A13/C, 1756-A13K/C, 1756-A17/B,
1756-A17K/B, 1756-A17/C, 1756-A17K/C, 1756-A4LXT/B, 1756-A5XT/B, 1756-A7LXT/B, 1756-A7XT/B, 1756-A7XT/C
The ControlLogix® system is a modular system that requires a 1756 ControlLogix chassis. The chassis are designed for only
horizontal back-panel mounting. Place any module into any slot. The backplane provides a high-speed communication
path between modules.
AutoCAD product drawings are available at http://www.rockwellautomation.com/en/e-tools/drawings.html.
Topic | Page |
Standard ControlLogix Chassis Specifications | 2 |
ControlLogix-XT Chassis Specifications | 4 |
Spacing Requirements | 6 |
ControlLogix Chassis with Standard Power Supplies Mounting Dimensions (Series B) |
8 |
ControlLogix Chassis with Standard Power Supplies Mounting Dimensions (Series C) |
12 |
ControlLogix Chassis Accessories | 20 |
Additional Resources | 21 |
IECEx | N/A |
IECEx System, compliant with: • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • IEC 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • IECExUL14.0008X |
|
KC |
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 |
||
EAC |
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation |
||
Certification(1) | 1756-A4/B | 1756-A7/B, 1756-A10/B, 1756-A13/B, 1756-A17/B |
1756-A4/C, 1756-A7/C, 1756-A10/C, 1756-A13/C, 1756-A17/C |
Attribute | 1756-A4LXT/B | 1756-A7LXT/B | 1756-A5XT/B | 1756-A7XT/B | 1756-A7XT/C |
Backplane current, chassis/slot max @ 1.2V DC | 1.5 A/- | ||||
Backplane current, chassis/slot max @ 3.3V DC | 4 A/4 A | ||||
Backplane current, chassis/slot max @ 5.1V DC | 10 A/6 A | 15 A/6 A | 10 A/6 A | ||
Backplane current, chassis/slot max @ 24V DC | 2 A/2 A | 2.8 A/ 2.8A | 2 A/2 A | ||
Power dissipation, max | 3.7 W | 4.1 W | 4.4 W | ||
Isolation voltage | Determined by installed power supply and modules | ||||
Slots | 4 | 7 | 5 | 7 | |
Mounting method | Horizontal only | ||||
Cabinet size (HxWxD), min |
50.8 x 50.8 x 20.3 cm (20 x 20 x 8 in.) |
50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) |
50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.) |
50.8 x 60.9 x 20.3 cm (20 x 24 x 8 in.) |
|
Weight, approx | 0.75 kg (1.7 lb) | 1.1 kg (2.4 lb) | 1.45 kg (3.2 lb) | 1.09 kg (2.4 lb) | |
Location | Panel | ||||
Wire size |
Functional earth ground - 8.3 mm2 (8 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater Protective earth ground - 2.1 mm2 (14 AWG) solid or stranded copper wire rated at 90 °C (194 °F) or greater |
||||
North American temperature code | T5 | T4A | T4 | ||
IEC temperature code | T5 | T4 | |||
Enclosure type rating | None (open-style) |
Attribute | 1756-A4LXT/B, 1756-A7LXT/B | 1756-A5XT/B, 1756-A7XT/B | 1756-A7XT/C |
Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) |
-25…60 °C (-13…140 °F) | -25…70 °C (-13…158 °F) | |
Temperature, surrounding air | 60 °C (140 °F) | 70 °C (158 °F) | |
Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) |
-40…85 °C (-40…185 °F) | ||
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) |
5…95% noncondensing | ||
Vibration IEC 60068-2-6 (Test Fc, Operating) |
2 g @ 10…500 Hz | ||
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
30 g | ||
Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) |
50 g | 30 g | |
Emissions | IEC 61000-6-4 | ||
ESD immunity IEC 61000-4-2 |
6 kV contact discharges 8 kV air discharges |
||
Radiated RF immunity IEC 61000-4-3 |
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz |
Certification(1) | 1756-A5XT/B, 1756-A7XT/B, 1756-A7XT/C | 1756-A4LXT/B, 1756-A7LXT/B |
c-UL-us |
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. |
|
FM | FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations. | |
CE |
European Union 2004/108/EC EMC Directive, compliant with: • EN 61326-1; Meas./Control/Lab., Industrial Requirements • EN 61000-6-2; Industrial Immunity • EN 61000-6-4; Industrial Emissions • EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) |
|
RCM |
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions |
|
Ex |
European Union 94/9/EC ATEX Directive, compliant with: • EN 60079-15; Potentially Explosive Atmospheres, Protection “n” • EN 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc X • DEMKO13ATEX1325026X |
|
IECEx |
IECEx System, compliant with: • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • IEC 60079-0; General Requirements • II 3 G Ex nA IIC T4 Gc • IECExUL14.0008X |
IECEx System, compliant with: • IEC 60079-15; Potentially Explosive Atmospheres, Protection "n" • IEC 60079-0; General Requirements • II 3 G Ex nA IIC T5 Gc • IECExUL14.0008X |
KC |
Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 |
|
EAC |
Russian Customs Union TR CU 020/2011 EMC Technical Regulation Russian Customs Union TR CU 004/2011 LV Technical Regulation |