HCM
ATS48C21Q
Delivery time:in stock
range of product
Altistart 48
Product or component type
Soft starter
Product destination
Asynchronous motors
Product specific application
Heavy duty industry and pumps
Device short name
ATS48
Utilisation category
AC-53A
Ue power supply voltage
230...415 V - 15...10 %
power supply frequency
50...60 Hz - 5...5 %
Motor power kW
55 kW at 230 V connection in the motor supply line for standard applications
90 kW at 230 V connection to the motor delta terminals for severe applications
90 kW at 400 V connection in the motor supply line for severe applications
110 kW at 230 V connection to the motor delta terminals for standard applications
110 kW at 400 V connection in the motor supply line for standard applications
132 kW at 400 V connection to the motor delta terminals for severe applications
160 kW at 400 V connection to the motor delta terminals for standard applications
45 kW at 230 V connection in the motor supply line for severe applications
Device connection
To the motor delta terminals
In the motor supply line
Protection type
Phase failure: line
Thermal protection: motor
Thermal protection: starter
standards
EN/IEC 60947-4-2
Product certifications
GOST
SEPRO
CSA
C-Tick
NOM 117
TCF
UL
CCC
DNV
Marking
CE
Discrete input number
5
Discrete input type
PTC, 750 Ohm at 25 °C
(Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
Discrete input logic
Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
Minimum switching current
10 mA at 6 V DC for relay outputs
Discrete output number
2
Discrete output type
(LO1) logic output 0 V common configurable
(LO2) logic output 0 V common configurable
(R1) relay outputs fault relay NO
(R2) relay outputs end of starting relay NO
(R3) relay outputs motor powered NO
Analogue output type
Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
communication port protocol
Modbus
Connector type
1 RJ45
Communication data link
Serial
physical interface
RS485 multidrop
Transmission rate
4800, 9600 or 19200 bps
Function available
External bypass (optional)
operating position
Vertical +/- 10 degree
Height
380 mm
Width
320 mm
Depth
265 mm
Net weight
18.2 kg
Electromagnetic compatibility
Conducted and radiated emissions level A conforming to IEC 60947-4-2
Damped oscillating waves level 3 conforming to IEC 61000-4-12
Electrostatic discharge level 3 conforming to IEC 61000-4-2
Immunity to electrical transients level 4 conforming to IEC 61000-4-4
Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
Voltage/current impulse level 3 conforming to IEC 61000-4-5
Relative humidity
0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
Ambient air temperature for operation
40…60 °C (with current derating of 2 % per °C)
-10…40 °C (without derating)
Ambient air temperature for storage
-25…70 °C
Operating altitude
<= 1000 m without derating
> 1000...2000 m with current derating of 2.2 % per additional 100 m