KFD2-CD-Ex1.32
1
  • KFD2-CD-Ex1.32
2
views: 260

KFD2-CD-Ex1.32

Rate:
0.0000/5

( 0 reviews )

Item NO.: V029905 MOQ: 0
Weight:    0kgs
Package Size:  
 Price:
$76.10
 Qty:
      $76.10
 Shipping:   Calculate Shipping Cost
LSH
KFD2-CD-Ex1.32

delivery time: in stock  

General specifications
Signal type Analog output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 7+, 8-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Rated current current output: ≤ 50 mA ; voltage output: ≤ 20 mA
Power dissipation 1.2 W
Input
Connection side control side
Connection terminals 9+, 10-, 11+
Voltage drop optional current input: approx. 4 V at 20 mA
Input current ≤ 100 µA up to 50 °C (122 °F) at 10 V
Limit optional current input: Input current: approx. ≤40 mA
optional voltage input: input voltage: 12 V DC
Transmission range optional current input: 0 ... 20 mA/optional voltage input: 0 ... 10 V
Output
Connection side field side
Connection terminals 1+, 2-
Voltage optional current output: 17 V at 20 mA/optional voltage output: 0 ... 10 V
Current optional current output: 0 ... 20 mA/optional voltage output: ≤ 20 mA
Load optional current output: max. 850 Ω
optional voltage output: output resistance max. 3 Ω
Transfer characteristics
Accuracy 0.1 %
Deviation
After calibration ≤ ± 0.1 % incl. non-linearity and hysteresis at 20 °C (68 °F)
Influence of ambient temperature ≤ ± 0.01 %/K
Rise time < 10 ms
Galvanic isolation
Input/power supply functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elements LED
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2004
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate BAS 02 ATEX 7203 X
Marking Ex-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Voltage 25.2 V DC
Current optional current output: 93 mA
optional voltage output: 95 mA
Power optional current output: 0.586 W
optional voltage output: 0.59 W
Supply
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage 250 V (Attention! The rated voltage can be lower.)
Certificate TÜV 99 ATEX 1499 X
Marking Ex-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing 116-0129
UL approval
Control drawing 116-0173 (cULus)
IECEx approval
IECEx certificate IECEx BAS 05.0041
IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.


Classifications

System Classcode
ECLASS 11.0 27210120
ECLASS 10.0.1 27210120
ECLASS 9.0 27210120
ECLASS 8.0 27210120
ECLASS 5.1 27210120
ETIM 8.0 EC002653
ETIM 7.0 EC002653
ETIM 6.0 EC002653
ETIM 5.0 EC001485
UNSPSC 12.1 32101514


 
No comment