LC1D115M7
1
  • LC1D115M7
2
views: 755

LC1D115M7

Rate:
0.0000/5

( 0 reviews )

Item NO.: V031076 MOQ: 0
Weight:    2.5kgs
Package Size:  158*120*136mm
 Price:
$170.50
 Qty:
      $170.50
 Shipping:   Calculate Shipping Cost

HCM(WXM

LC1D115M7

Delivery time:2-3 weeks


Main
Range TeSys
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Contactor application Motor control
Resistive load
Utilisation category AC-4
AC-1
AC-3
AC-3e
Poles description 3P
[Ue] rated operational voltage Power circuit <= 1000 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 200 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
115 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
115 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
[Uc] control circuit voltage 220 V AC 50/60 Hz
Complementary
Motor power kW 30 kW 220...230 V AC 50/60 Hz AC-3)
55 kW 380...400 V AC 50/60 Hz AC-3)
59 kW 415...440 V AC 50/60 Hz AC-3)
75 kW 500 V AC 50/60 Hz AC-3)
80 kW 660...690 V AC 50/60 Hz AC-3)
65 kW 1000 V AC 50/60 Hz AC-3)
18.5 kW 400 V AC 50/60 Hz AC-4)
30 kW 220...230 V AC 50/60 Hz AC-3e)
55 kW 380...400 V AC 50/60 Hz AC-3e)
59 kW 415...440 V AC 50/60 Hz AC-3e)
75 kW 500 V AC 50/60 Hz AC-3e)
80 kW 660...690 V AC 50/60 Hz AC-3e)
65 kW 1000 V AC 50/60 Hz AC-3e)
Maximum Horse Power Rating 30 hp 200/208 V at AC 50/60 Hz for 3 phase
40 hp 230/240 V at AC 50/60 Hz for 3 phase
75 hp 460/480 V at AC 50/60 Hz for 3 phase
100 hp 575/600 V at AC 50/60 Hz for 3 phase
Compatibility code LC1D
Pole contact composition 3 NO
Contact compatibility M13
Protective cover With
[Ith] conventional free air thermal current 200 A 140 °F (60 °C) power circuit
Irms rated making capacity 1260 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
Rated breaking capacity 1100 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current 250 A 104 °F (40 °C) - 10 min power circuit
550 A 104 °F (40 °C) - 1 min power circuit
950 A 104 °F (40 °C) - 10 s power circuit
1100 A 104 °F (40 °C) - 1 s power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating 250 A gG <= 690 V type 1 power circuit
200 A gG <= 690 V type 2 power circuit
10 A gG signalling circuit
Average impedance 0.6 mOhm - Ith 200 A 50 Hz power circuit
Power dissipation per pole 24 W AC-1
7.9 W AC-3
7.9 W AC-3e
[Ui] rated insulation voltage Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 1000 V IEC 60947-4-1
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 8 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 8 Mcycles
Electrical durability 0.8 Mcycles 200 A AC-1 <= 440 V
0.95 Mcycles 115 A AC-3 <= 440 V
0.95 Mcycles 115 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits 0.3...0.5 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.15 Uc -40…131 °F (-40…55 °C) operational AC 50/60 Hz
1...1.15 Uc 131…158 °F (55…70 °C) operational AC 50/60 Hz
Inrush power in VA 280…350 VA 60 Hz 0.8 68 °F (20 °C))
280…350 VA 50 Hz 0.8 68 °F (20 °C))
Hold-in power consumption in VA 2…18 VA 60 Hz 0.3 68 °F (20 °C))
2…18 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation 3…8 W 50/60 Hz
Operating time 6...20 ms opening
20...50 ms closing
Maximum operating rate 2400 cyc/h 140 °F (60 °C)
Connections - terminals Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.00 in² (1…2.5 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) solid without cable end
Power circuit connector 1 0.02…0.19 in² (10…120 mm²) flexible without cable end
Power circuit connector 2 0.02…0.08 in² (10…50 mm²) flexible without cable end
Power circuit connector 1 0.02…0.19 in² (10…120 mm²) flexible with cable end
Power circuit connector 2 0.02…0.08 in² (10…50 mm²) flexible with cable end
Power circuit connector 1 0.02…0.19 in² (10…120 mm²) solid without cable end
Power circuit connector 2 0.02…0.08 in² (10…50 mm²) solid without cable end
Tightening torque Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals Philips No 2
Power circuit 106.21 lbf.in (12 N.m) connector hexagonal 0.16 in (4 mm)
Control circuit 10.62 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V signalling circuit
Minimum switching current 5 mA signalling circuit
Insulation resistance > 10 MOhm signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
Product Certifications RINA
CSA
CCC
BV
LROS (Lloyds register of shipping)
GL
GOST
DNV
UL
UKCA
IP degree of protection IP20 front face IEC 60529
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device -40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Operating altitude 0...9842.52 ft (0...3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor closed 15 Gn for 11 ms)
Shocks contactor open 6 Gn for 11 ms)
Height 6.22 in (158 mm)
Width 4.72 in (120 mm)
Depth 5.35 in (136 mm)
Net Weight 5.51 lb(US) (2.5 kg)

 
No comment
Total 0 records, divided into1 pages. First Prev Next Last
View History
Related tools
$66.50
$275.50
$49.00
$11.00
$86.00
$39.00
$1413.10
$21.00
$28.50
Business time
9:00-22:00
  • Email:support@rig123.com