HCM(ZXG)
IB IL 24 PSDO 8-PAC-2985631
Delivery time:4-5 months
Dimensional drawing | |
Width | 48.8 mm |
Height | 119.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Inline local bus | |
No. of channels | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps / 2 Mbps (can be switched) |
Module | |
ID code (dec.) | 167 |
ID code (hex) | A7 |
Length code (hex) | 04 |
Length code (dec) | 04 |
Process data channel | 8 Byte |
Input address area | 8 Byte ((Operating mode: SafetyBridge)) |
Output address area | 8 Byte ((Operating mode: SafetyBridge)) |
Register length | 8 Byte |
Required parameter data | 1 Byte ((Operating mode: SafetyBridge)) |
Required configuration data | 5 Byte ((Operating mode: SafetyBridge)) |
Digital | |
Output name | Digital outputs |
Connection method | Spring-cage connection |
Connection technology | 2-, 3-conductor |
Number of outputs | 4 (for 2-channel assignment) |
8 (for 1-channel assignment) | |
8 | |
Protective circuit | Overload protection, short-circuit protection of outputs |
Output voltage | 24 V DC (US - 1 V) |
Output current | max. 6 A (Total current of all outputs, -25 °C ... 50 °C) |
max. 4 A (Total current of all outputs, >50 °C ... 55 °C) | |
Maximum output current per group | 3 A |
Maximum output current per channel | 2 A |
Maximum output current per module | 3 A (See technical data) |
Nominal output voltage | 24 V DC |
Nominal load, inductive | see safety data |
Nominal load, lamp | see safety data |
Nominal load, ohmic | see safety data |
Behavior with inductive overload | Output can be destroyed |
Type | modular |
Product type | I/O component |
Product family | Inline |
Application | Functional safety |
Diagnostics messages | Short-circuit or overload of the digital outputs Error message in diagnostics code (bus) and display by means of the LED on the motor |
Maximum power dissipation for nominal condition | 144 W |
Transmission medium | Copper |
Potentials: Communications power (UL) | |
Supply voltage | 7.5 V DC (see safety data) |
Current draw | max. 230 mA (see safety data) |
Potentials: Main circuit supply (UM) | |
Supply voltage | 24 V DC |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 6.03 A |
typ. 30 mA (all outputs set including actuator current) | |
Supply: Module electronics | |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 30 V DC |
Connection technology | |
Connection name | Inline connector |
pluggable | yes |
Conductor connection | |
Connection method | Spring-cage connection |
Conductor cross section solid | 0.2 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Inline connector | |
Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
Conductor cross section AWG | 24 ... 16 |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 |
Air pressure (operation) | 80 kPa ... 108 kPa (up to 2000 m above sea level) |
Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Permissible humidity (operation) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Permissible humidity (storage/transport) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |