HCM(ZXG)
IB IL AI 2/SF-PAC-2861302
Delivery time:in stock
Dimensional drawing | |
Width | 12.2 mm |
Height | 136.8 mm |
Depth | 71.5 mm |
Note on dimensions | Housing dimensions |
Utilization restriction | |
CCCex note | Use in potentially explosive areas is not permitted in China. |
Color | green |
Inline local bus | |
Number of interfaces | 2 |
Connection method | Inline data jumper |
Transmission speed | 500 kbps |
Module | |
ID code (dec.) | 127 |
ID code (hex) | 7F |
Length code (hex) | 02 |
Length code (dec) | 02 |
Process data channel | 32 Bit |
Input address area | 4 Byte |
Output address area | 4 Byte |
Register length | 32 Bit |
Required parameter data | 6 Byte |
Required configuration data | 4 Byte |
Analog | |
Input name | Analog inputs |
Description of the input | Single-ended inputs, voltage or current |
Number of inputs | 2 |
A/D conversion time | typ. 120 µs (per channel) |
Connection method | Inline shield connector |
Connection technology | 2-conductor |
Note regarding the connection technology | shielded |
Current input signal | 0 mA ... 20 mA |
4 mA ... 20 mA | |
-20 mA ... 20 mA | |
Input resistance current input | 50 Ω (Shunt) |
Voltage input signal | 0 V ... 10 V |
-10 V ... 10 V | |
Input resistance of voltage input | > 220 kΩ |
Data formats | IB IL, IB ST, IB RT, standardized representation |
Limit frequency (3 dB) | 40 Hz |
Common mode voltage range signal - ground | 40 V (Between current input and functional ground) |
40 V (between voltage input and functional ground) | |
Measuring principle | Successive approximation |
Measured value resolution | 16 bits (15 bits + sign bit) |
Measured value representation | 16 bit two's complement |
Protective circuit | Surge protection; Suppressor diodes in the analog inputs |
Type | modular |
Product type | I/O component |
Product family | Inline |
Scope of delivery | including Inline connector and labeling field |
Operating mode | Process data operation with 2 words |
Diagnostics messages | Failure of the internal I/O supply Yes |
I/O error Error message in the process data | |
User error Error message in the process data | |
Insulation characteristics | |
Overvoltage category | II (IEC 60664-1, EN 60664-1) |
Pollution degree | 2 (IEC 60664-1, EN 60664-1) |
Maximum power dissipation for nominal condition | 1.87 W |
Potentials | |
Power consumption | typ. 662 mW |
max. 882 mW | |
Potentials: Communications power (UL) | |
Supply voltage | 7.5 V DC (via voltage jumper) |
Current draw | max. 60 mA |
typ. 45 mA | |
Potentials: Supply of analog modules (UANA) | |
Supply voltage | 24 V DC (via voltage jumper) |
Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
Current draw | max. 18 mA |
typ. 13 mA |
Connection technology | |
Connection name | Inline connector |
Conductor connection | |
Connection method | Spring-cage connection |
Conductor cross section solid | 0.08 mm² ... 1.5 mm² |
Conductor cross section flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Inline connector | |
Connection method | Spring-cage connection |
Conductor cross section, rigid | 0.08 mm² ... 1.5 mm² |
Conductor cross section, flexible | 0.08 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Stripping length | 8 mm |
Ambient conditions | |
Ambient temperature (operation) | -25 °C ... 55 °C |
Degree of protection | IP20 |
Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
80 kPa ... 106 kPa (up to 3000 m above sea level, in ATEX Zone 2) | |
Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
Ambient temperature (storage/transport) | -25 °C ... 85 °C |
Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting type | DIN rail mounting |