HCM
PVSE 400/24-10
Delivery time:1 week
Input | |
---|---|
Input rated voltage | 3 x 400 - 500 Vac |
Input voltage range | 340 - 550 Vac (480 - 780 Vdc) |
Input rated current (rated load) | 0.6 A (3 x 340 Vac) |
Rated frequency range | 44 Hz - 66 Hz / 0 Hz |
Starting current limiter | <30 A, NTC |
Input fuse internal | 3 x 1.6 A (slow-blow) |
Recommended back-up fuse (circuit breaker) | 6 A, 10 A, 16 A, characteristics B, C |
Harmonic correction | passive |
Mains buffering (rated load) |
22.6 / 51.5 ms (400 / 500 Vac) |
Transient surge voltage protection | Varistor |
Output | |
---|---|
Output rated voltage | 24 Vdc |
Output voltage range | 22.8 - 28.8 Vdc |
Resistance to reverse feed max. | 35 Vdc |
Output rated current | 10 A |
Parallel connection | Yes |
Power Boost | 20 A / 4 s (15 A / 8 s) |
Overload behaviour | Constant current |
max. Power loss idling/nominal load | 7.8 / 19.9 W |
Serial operation | Yes |
Efficiency | typ. 91.7 % |
Ripple factor | typ. 70 mVss |
Top Boost | 70 A / 50 ms |
Signaling | |
---|---|
Power Good (DC OK) | LED green, LED red |
Potential-free signal contact | Yes |
Stand-by-input | Yes |
Approvals | |
---|---|
Approvals | cURus, cULus |
Environment | |
---|---|
Ambient temperature | -13 °F to 158° F |
Storage temperature | -13 °F to +185 °F |
Derating | -3 %/K > +122 °F |
Safety and protection | |
---|---|
Protection index | IP 20 |
Safety class | I, with PE connection |
Terminal and mounting | |
---|---|
Terminals input, (spring clamp terminal, pluggable) | max. 2.5 mm² |
Terminals output, (spring clamp terminal, pluggable) | max. 2.5 mm² |
Terminals signalling, (spring clamp terminal, pluggable) | max. 0.5 mm² |
Mounting position | vertical |
Fixing method | DIN Rail system TS35 |
Measures and weights | |
---|---|
Width | 2.24 inch |
Height | 5.00 inch |
Depth | 7.07 inch |
Weight | 2.87 lbs |
Accessory | |
---|---|
Connector for signalling | PV-CON (optional) |
Side DIN rail mounting | PV-TS35M (optional) |
Direct screw fastening plate for lateral mounting | PV-WB2 (optional) |